The ZP710Ex-1 intrinsically
safe, analogue, ionization, smoke
sensor is designed to provide reliable
sensing of both visible and invisible
products of combustion from fast
burning fires, within areas made
hazardous by the presence of explosive
gasses.
Intrinsic safety is
a technique for ensuring that items
of electrical equipment and their
associated wiring are incapable
of releasing sufficient electrical
and thermal energy to cause ignition,
when installed within areas where
hazardous concentrations of explosive
gasses may permanently, or from
time to time, be present.
The
ZP720Ex-1 intrinsically safe, analogue,
heat detector, is a thermistor controlled
device responding to changes in
ambient temperature, within areas
made hazardous by the presence of
explosive gasses.
Intrinsic safety is
a technique for ensuring that items
of electrical equipment and their
associated wiring are incapable
of releasing sufficient electrical
and thermal energy to cause ignition,
when installed within areas where
hazardous concentrations of explosive
gasses may permanently, or from
time to time, be present.
ZP740Ex-1
Intrinsically Safe Addressable Line
Interface Unit, PS1543.2
Designed
to provide an interface, onto the
fire alarm system for associated
equipment, the ZP740Ex-1 can be
configured to accept a variety of
input types, within areas made hazardous
by the presence of explosive gasses.
Intrinsic safety is
a technique for ensuring that items
of electrical equipment are incapable
of releasing sufficient electrical
and thermal energy to cause ignition,
when installed within areas where
hazardous concentrations of explosive
gasses may permanently, or from
time to time be present.
The
ZP786Ex-1 intrinsically safe callpoint,
provides a manual means of raising
an alarm within areas made hazardous
by the presence of explosive gasses.
Intrinsic safety
is a technique for ensuring that
items of electrical equipment and
their associated wiring are incapable
of releasing sufficient electrical
and thermal energy to cause ignition,
when installed within areas where
hazardous concentrations of explosive
gasses may permanently, or from
time to time, be present.
ZP-LC2
Intrinsically Safe Line Voltage Conditioner,
PS1308.2
The
ZP-LC2 Line Voltage Conditioner
permits intrinsically safe analogue
addressable sensors to be connected
to a ZP wiring loop. Each line conditioner
reduces ZP line voltages to a level
suitable for supply to an intrinsically
safe wiring tee off, via a compatible
EEx zener barrier.
Intrinsically
safe devices can be installed in
hazardous areas, where the presence
of explosive gasses in the atmosphere,
could be ignited by electrical or
thermal energy derived from the
fire detection equipment itself.
ZBM5
Linear Beam Detector, PS1433.3
Designed for use in
large, open, high ceiling areas
where point type detection would
prove difficult to install and maintain,
the ZBM5 linear beam detector provides
accurate detection of both smoke
and heat, from a variety of fire
conditions.
Compatible with
all Ziton analogue and conventional
systems the detection equipment
comprises a transmitter unit (Tx),
a receiver (Rx) and an optional
keypad controller.
Linear beam
smoke detectors have been developed
for use in areas where point type
detectors would be difficult to
install and maintain.
Two versions are available,
the ZBMR conventional and the ZP7BMR
addressable, both available with
detection ranges of either 50 or
100 metres.
ZLSS1
LaserSense 25 High Sensitivity Smoke
Detector, PS1837.1
LaserSense
25 is a high sensitivity smoke sensor
designed to give the earliest possible
warning of fire.
Smoke from the protected
area is drawn through the LaserSense
detector and analysed twice every
second by a laser pulse. Over a
period of 24 hours smoke pollution
distribution in the protected environment
is compiled and a databank created.
ZLSS2
LaserSense 100 High Sensitivity Smoke
Detector, PS1838.1
LaserSense
100 is a high sensitivity smoke
sensor designed to give the earliest
possible warning of fire.
Smoke from the
protected area is drawn through
the LaserSense detector and analysed
twice every second by a laser pulse.
Over a period of 24 hours smoke
pollution distribution in the protected
environment is compiled and a databank
created.
ZLSS4-LCD
LaserSense Ultra High Sensitivity
Smoke Detector, PS1840.1
LaserSense Ultra is
a high sensitivity smoke sensor
designed to give the earliest possible
warning of fire.
Smoke from protected
areas is drawn through the LaserSense
detector and analysed twice every
second by a laser pulse. Over a
period of 24 hours smoke pollution
distribution in the protected environment
is compiled and a databank created.
ZS600
Smoke Hound Basic, PS1434.2
Designed for applications
where aspiration equipment is specified,
but where the high sensitivity,
normally inherent in these devices
is an unnecessary expense, or at
times a nuisance due to unwanted
alarms, the Smoke Hound Basic provides
a practical solution, by allowing
the use of standard point type detectors
within an aspirated enclosure.
In areas such
as floor and ceiling voids, data
processing equipment, bank vaults
and prison cells, the unit can be
installed to provide a practical,
cost effective sensing solution.